Combustion Flow Controllers: Initial Fault Checks

Knowledge Library

If a gas mass flow controller in a combustion application does not operate normally, check external conditions before assuming an internal failure.

Five initial checks

  1. Wiring: verify power, command, feedback and signal reference against the exact pinout. Safely isolate the system before changing wiring.
  2. Pressure: confirm inlet and outlet conditions match the ranges agreed when ordering.
  3. Restrictions: check for blocked tubing, sharp bends or other flow bottlenecks.
  4. Gas cleanliness: confirm the gas is dry and free of particles, liquid carryover and oil contamination.
  5. Command and feedback: verify the actual electrical signals. For a 0–5 V command, zero flow normally corresponds to 0 V; for a 4–20 mA command, zero flow normally corresponds to 4 mA. Do not apply a voltage example to a current input.

A wiring correction can restore operation only if the instrument has not already been damaged. Suspected circuit damage or sensor contamination requires manufacturer analysis or repair.

Gas-flow regulation does not replace the approved burner safeguards or independent isolation required by the combustion system. Perform any testing with a safe gas-handling arrangement and qualified personnel.

Gas flow application reference

Flowmethod designs, develops, manufactures and supports gas mass flow controllers, meters and custom gas-control and mixing systems. Configurations are matched to the customer's process and operating requirements.

For selection, installation or technical enquiries, contact Flowmethod: Mr. Dou, +86 180 3818 3381; doufeijin@hotmail.com. See Contact for the full contact list.

Ask an engineer

Share your process requirements so we can discuss suitable series and configurations.

Create a draft, then send to both recipients using Gmail or Outlook.

View full contact details →